1. Put Great interlock into the boiler;
2. Put the probe into theboilerfurnace;
3. Calloutinduced draft fanscreen,startit;
4. Close the induced draft fan inlet baffle;
5. Close the induced draft fan outlet baffle;
6. Start the induced draft fan motor (motorturns to greenfrom red on the screen);
7. After25 seconds, open induced draft fan outlet baffle;
8. callout the blowerscreen, start operation;
9. Close the blower inlet baffle;
10. Close the bloweroutletbaffle;
11. Start the blower motor (motorturns to greenfrom red on the screen);
12. After15 seconds,open theblower outlet baffle;
13. Start the inlet damper of the induced draft fan and the blower,keepthe pressure in the chamber about 50-100Pa;
14. Put small interlocking, callout the secondary air system screen, adjust secondary air damper in the purge position (30% to 40%);
15. The "oil leak test" screen, passleak test;
16. Callout"furnace purge" screen, press the Purge button;
17. Calloutthe fuel screen, adjust the oil pressure to 2.4Mpa;
18. Contact other staff, ready to fire the boiler;
19. Calloutoil system screen, press "start" buttonof oilgun, oil gun automaticallypurge, ignite. The oil gun torch is red.There ischartdisplay fire detection;